(i) Steel: As=4×π(1.25×10−2)2=1.96×10−3 m2.
Concrete: Ac=0.30×0.30−1.96×10−3=0.0880 m2.
So As=1.96×10−3 m2 (about 2.2% of the section) and Ac=0.0880 m2.
(ii) The bars are bonded to the concrete along the whole length and both are squeezed between the same top and bottom surfaces, so both shorten by the same amount. Equal lengths and equal shortenings mean equal strains. The load is shared: F=σcAc+σsAs=ε(YcAc+YsAs).
YcAc+YsAs=30×109×0.0880+200×109×1.96×10−3=2.64×109+3.93×108=3.03×109 N
ε=3.03×1091.0×106=3.30×10−4
The common strain is 3.30×10−4.
(iii)
σc=Ycε=30×109×3.30×10−4=9.89×106 Pa,σs=Ysε=200×109×3.30×10−4=6.59×107 Pa
Concrete: 9.89 MPa; steel: 65.9 MPa. For the same strain, the stiffer steel carries 200/30=6.7 times the stress.
(iv) Force in the steel: Fs=6.59×107×1.96×10−3=1.29×105 N, which is
1.0×1061.29×105=12.9%
of the load. The steel, only 2.2% of the area, carries about 12.9% of the load.
(v) Shortening of the reinforced column: ΔL=εL=3.30×10−4×3.0=9.89×10−4 m≈ 0.99 mm.
Plain concrete column (area 0.090 m2):
σ=0.0901.0×106=1.11×107 Pa,ΔL=YcσL=30×1091.11×107×3.0=1.11×10−3 m