(a)
P=VI=220×16=3520 W
So circuit 2 can supply about 3.5 kW in total — enough for a kettle and a television together, but not for several heaters at once.
(b) Because the cable feeding each circuit is chosen to match the load it has to carry.
Lights and fans draw very little current — a whole room of LED lamps may take well under an ampere — so the lighting circuit is wired in thin, cheap cable, and a 6 A breaker is all it needs. An air conditioner draws a large current continuously, so its circuit is wired in much thicker cable and given a breaker to match.
Using one heavy cable everywhere would work electrically, but it would be far more expensive and much harder to install.
(c) Because an MCB protects the cable, not the appliance.
Circuit 3 is wired in cable that is safe up to about 20 A, and the 20 A breaker is what guarantees the current never goes past that. Fit a 32 A breaker and the protection is simply removed: up to 32 A would now be allowed to flow through cable rated for 20 A. The cable would overheat inside the wall, where nobody can see it, smell it or reach it — and the first sign of trouble would be a fire in the ceiling.
A breaker that trips is doing its job. It is reporting that the circuit is being asked for more current than it was built for.
What the electrician should do instead:
- look for a fault — a short circuit, a faulty air conditioner, or something else plugged into the same circuit;
- if the load is genuinely too large for the circuit, rewire it in thicker cable first, and only then fit a larger breaker.
The order matters. The cable decides the breaker; the breaker never decides the cable.