(a) Each appliance is across the full 220V, so I=P/V:
Idrill=220400≈1.82A,Ilamps=220600≈2.73A
Itotal=1.82+2.73≈4.55A
(b) Yes. The total of about 4.55A is below the 5A rating, so the fuse carries this load without melting — though with very little margin to spare.
(c) The heater adds
Iheater=220500≈2.27A
Itotal=4.55+2.27≈6.82A
This exceeds 5A, so the fuse wire melts and breaks the circuit — which is exactly what it is there to do, protecting the wiring from overheating.
(d) He should run the heater on a separate circuit with its own suitably rated fuse, rather than fitting a larger fuse to the existing one. Replacing the fuse with a higher-rated one would let the wiring carry more current than it was designed for, creating a fire risk.