(i) A fuse is rated 8A. Can it be used with an electrical appliance rated 5 KW, 200 V? Give a reason.
(ii) Name two safety devices which are connected to the live wire of a household electric circuit.
Confirming your payment
Sign up now and get 250 free tokens.
Previous Year Questions · Question 8 of 27
(i) A fuse is rated 8A. Can it be used with an electrical appliance rated 5 KW, 200 V? Give a reason.
(ii) Name two safety devices which are connected to the live wire of a household electric circuit.
Solution:
Concept: A rating such as '1540 W, 220 V' means the appliance uses that power when connected to that voltage. Its normal working current is I = P ÷ V, and a fuse used with it must be rated a little above this current, or it would melt as soon as the appliance is switched on. Only the live wire is at a high potential (220 V); the neutral and the earth are at 0 V. A device that is meant to make an appliance safe (a fuse, an MCB or a switch) must therefore cut it off from the live wire.
Given: Fuse 8 A; appliance 5 kW, 200 V.
Step 1 — Find the current drawn (part i).
The appliance draws a current I = P ÷ V, with the power 5 kW written as 5000 W.
Step 2 — Compare with the fuse (part i).
The appliance draws 25 A, much more than 8 A, so the 8 A fuse wire would melt as soon as the appliance is switched on. A fuse of rating a little more than 25 A is needed.

Step 3 — Name two safety devices (part ii).
The fuse (or MCB) breaks the circuit when the current becomes too large, and the switch, in the off position, cuts the appliance off from the high potential of the live wire, so it is safe to touch or repair.
Watch out: Change 5 kW into 5000 W before dividing by the voltage.
Therefore, (i) no: the appliance draws 25 A, more than the 8 A rating, so the fuse would melt; (ii) the fuse (or MCB) and the switch.