Speed regulators. A ceiling fan is rated 110 W at 220 V, 50 Hz. For this case study, treat it as a resistive load. To run it slowly, its current must be halved. Older regulators did this with a series resistor. Better ones used a series choke (an inductor of negligible resistance).
(a) Find the fan's resistance and its normal current.
(b) What series resistance halves the current? How much power is then wasted in the regulator?
(c) What inductance would halve the current instead? How much power is wasted in it?
(d) Find the power drawn from the mains in each case, and the power factor with the choke. Which regulator is better, and why?
(a)
R=PV2=1102202=440Ω,I=220110=0.50A
(b) For 0.25 A the total impedance must be 0.25220=880Ω, so the series resistor is 880−440=440Ω. It wastes
I2R=0.252×440=27.5W
(c) Now 4402+XL2=880:
XL=8802−4402=762Ω,L=2π×50762=2.43H
An ideal choke wastes no power, since its current is wattless.
(d) In both cases the fan gets 0.252×440=27.5 W.
Resistor regulator: the mains supplies 27.5+27.5=55 W (power factor 1). Half of it is lost as heat in the regulator.
Choke regulator: the mains supplies only 27.5 W. The power factor is ZR=880440=0.5.
The choke is better. It controls the current through its reactance, which consumes no energy, so the regulator stays cool and the electricity bill is lower. (Modern electronic regulators achieve the same with even smaller components.)