(a)
I=VcosϕP=220×0.62200=16.7 A
With sinϕ=0.8:
- power component: Icosϕ=10.0 A (in phase with V)
- wattless component: Isinϕ=13.3 A (lagging V by 90∘)
(b) The capacitor must draw a current of 13.3 A leading V by 90∘, which cancels the wattless component:
IC=VωC⇒C=220×2π×5013.3=1.93×10−4 F=193 μF

(c) Only the power component remains, so the supply provides 10.0 A instead of 16.7 A. The load still has 220 V across it and still takes its 16.7 A and 2.2 kW. Only the supply line's current is reduced, and with it the I2R loss in the line.
(d) In parallel, the load keeps the full supply voltage and works exactly as before. In series, the capacitor would change the current through the load and the voltage across it. It could even create a series resonance with the load's inductance, driving dangerously high voltages. The parallel capacitor simply supplies the wattless current locally.