Option (A) is correct.
Concept used — average power and power factor
P=VrmsIrmscosϕ⇒Irms=VrmscosϕP
For a fixed useful power P at a fixed supply voltage, the current needed is inversely proportional to the power factor cosϕ.
Step 1 — Judge the Assertion. A lower power factor makes the denominator Vrmscosϕ smaller, so a larger current is needed for the same useful power. For example, halving cosϕ doubles Irms. A is true.
Step 2 — Judge the Reason. P=VrmsIrmscosϕ is the correct expression for the average power; with P and Vrms fixed, a fall in cosϕ must be made up by a rise in Irms. R is true.
Step 3 — Does R explain A? Rearranging R gives Irms=VrmscosϕP, which is the statement of A. R is the correct explanation of A.
Answer: both A and R are true and R explains A, option (A).
Note: the extra current heats the supply cables (I2R loss), which is why supply companies want consumers' power factor close to 1.