Option (B) is correct.
Concept used — true power, apparent power and power factor
The true (average) power taken by a load is
P=VrmsIrmscosϕ⇒Irms=VrmscosϕP
so for a given power, a low power factor means a large supply current.
Step 1 — Write the given values. True power P=100 kW=1.00×105 W, supply voltage Vrms=400 V, power factor cosϕ=0.6 (lagging).
Step 2 — Find the current before correction.
Irms=400×0.61.00×105=2401.00×105=417 A
Answer: the factory draws about 417 A, option (B).

The 417 A current lags V; the capacitor bank cancels its wattless part, leaving the in-phase part.
Why the others fail: (A) 250 A =400105 is the current at unity power factor (the in-phase part of the 417 A, reached only after full correction). (C) 167 is the apparent power in kVA, 0.6100=167 kVA, not a current. (D) 500 A =400×0.5105 would need a power factor of 0.5.
Note: the apparent power before correction is VrmsIrms=400×417=167 kVA; after correction to cosϕ=1 it falls to 100 kVA, and the line loss I2R falls by (417/250)2≈2.8 times.