(a) Area A=1.0×1.5=1.5 m2, thickness L=4.0×10−3 m.
H=LKAΔT=4.0×10−30.8×1.5×20=6.0×103 W
Through a single pane: 6000 W.
(b) The figure of 6000 W assumes that the two faces of the glass are at the full room and outdoor temperatures. In reality a thin layer of almost still air clings to each face of the glass. Air is a very poor conductor, so most of the temperature difference between the room air and the outdoor air is used up across these air films, and the glass itself has only a small temperature difference across it. The heat flow is therefore much smaller.
(c) In the steady state the same heat current H passes through each layer in turn, so the temperature drops across the layers add up to 20 K. For each layer ΔTi=HLi/(KiA), so
20=AH(0.84.0×10−3+0.02410×10−3+0.84.0×10−3)=AH(0.005+0.4167+0.005)=AH×0.4267
H=0.42671.5×20=70.3 W
Double glazing loses about 70 W, which is 6000/70.3≈85 times less than a single pane.
(d) The heat flux is H/A=70.3/1.5=46.9 W m−2. The drop across each layer is (H/A)(L/K):
ΔTglass=46.9×0.005=0.23 K,ΔTair=46.9×0.4167=19.5 K
Almost all the drop, 19.5 K of the 20 K, occurs across the 10 mm air layer, because still air conducts about 33 times worse than glass and the layer is also thicker. The glass panes hardly matter; the trapped air does the insulating. (The gap is kept narrow so that the air does not circulate and carry heat by convection.)