(a) Each appliance is across the full 220V, so the powers add and I=P/V:
Ptotal=2000+750+5×100=3250W
I=2203250≈14.8A
(b) Yes. 14.8A is below the 15A rating, so the fuse carries this load. But the largest power the circuit can supply is
Pmax=VI=220×15=3300W
Only 3300−3250=50W is spare, so not even one more 100 W bulb can be added: with six bulbs the current would be 3350/220≈15.2A, and the fuse would blow.
(c) Without the heater, the power available for the bulbs is 3300−750=2550W.
1002550=25.5
So at most 25 bulbs can be on with the iron: 25 bulbs and the iron draw 3250/220≈14.8A, while 26 bulbs would draw 3350/220≈15.2A.
(d) No. The heater alone draws
I=2202000≈9.1A
which is more than 5A. The current would heat the 5 A fuse wire until it melts, and the circuit would break as soon as the heater is switched on. A heater needs a circuit and fuse of higher current rating.