The power generated at the generating station is transmitted to the main sub station at voltage :
Household Circuits · Question 3 of 73
The power generated at the generating station is transmitted to the main sub station at voltage :
(A) 33 kV
(B) 11 kV
- Correct answer
(C) 132 kV
(D) none of these
Answer: (C) 132 kV
Concept: For a given power P = VI, the current is I = P ÷ V, so a higher voltage means a smaller current. The heat wasted in line wires of resistance R in time t is H = I²Rt, so a smaller current wastes much less energy as heat.
Step 1 — Step the voltage up.
At the grid sub-station near the power station, a step-up transformer raises the voltage from 11 kV to 132 kV, so that the current in the long line wires is small.
Step 2 — Follow the power to the main sub-station.
The power then travels along the transmission lines at 132 kV and reaches the main sub-station at this voltage. Only there is it stepped down to 33 kV.

Watch out: The main sub-station RECEIVES the power at 132 kV; 33 kV is the voltage that LEAVES it.
Why the other options are wrong:
- (A) 33 kV: 33 kV is the voltage after the step-down at the main sub-station, so it leaves the main sub-station; it does not arrive there.
- (B) 11 kV: 11 kV is the generating voltage, before the step-up; power is never sent over long lines at this low voltage.
- (D) none of these: 132 kV is one of the options, (C), so 'none of these' cannot be right.
Therefore, the power is transmitted to the main sub-station at 132 kV, option (C).