Question 333 marksMedium
Competency: Analysis
A power station sends 3.3 MW of power to a town through line wires of total resistance 10 . The bar graph shows the heat lost per second in the line wires when the same power is sent at four different voltages. (Hypothetical data.)

(a) By what factor does the heat loss fall when the voltage is raised from 11 kV to 33 kV?
(b) Show, using the bars for 33 kV, 66 kV and 132 kV, that the loss is inversely proportional to the square of the voltage.
(c) Use this rule to predict the heat loss at 22 kV, and check it by calculating the current in the line at 22 kV and the heat .