Competency: Analysis & Application
The local earthing of a house is a copper plate buried in a pit about 2.5 m deep and surrounded by a mixture of charcoal and salt. After a long dry summer an electrician finds that the resistance of the path from the earth wire of the house to the ground has risen from 2 Ω to 55 Ω.
(a) Suggest why the resistance has risen, and a simple way to bring it down.
(b) The live wire of a geyser on the 220 V mains, protected by a 15 A fuse, comes in contact with its metal body. Taking the resistance of the rest of the path to be negligible, calculate the current through the earth wire for each value of the resistance, and hence explain why the dry earthing is dangerous.