(a) Two reasons:
- Every appliance gets the full mains voltage. In parallel each one is connected straight across the supply, so each receives the 220V it is designed for. In series the voltage would be divided between them and none would work properly.
- Each appliance works independently. A fault in one, or simply switching it off, leaves the others running, because each has its own separate path for the current. In series a single break would stop everything.
(b) Work out the current each appliance draws:
Iheater=VP=2201500≈6.82A
Ilamp=220100≈0.45A
In parallel the currents add:
Itotal≈6.82+0.45=7.27A
Yes, the fuse will blow. The total current of about 7.27A is well above the fuse's 5A rating, so the fuse wire melts and breaks the circuit — which is exactly what it is there to do.