I=VP=2201200+400=2201600≈7.3A
(b) A 5A fuse would melt every time both appliances were on, although nothing is wrong. A 10A fuse would allow currents between 8A and 10A to flow without melting, and the wiring is not safe at those currents; it could overheat, so the fuse would not be protecting the wiring.
(c) Do not run both on this circuit. Move the kettle (which alone draws 2201200≈5.5A) to a separate circuit with its own suitable fuse. The refrigerator alone draws only 220400≈1.8A, so it is then safely protected by the 5A fuse.